| |
BACKFLOW PREVENTION
InformationRules and Regulations
Backflow regulations are outlined in the National Plumbing Code of
Canada, 1995 edition. Protection from contamination is briefly described
in the section 6.2 of the Code. The Code also incorporates the Canadian
Standards Association (CSA) B64.10 Standard which is more detailed than
the Code. The Code can be obtained through the Queens Printers (780) 427-4952
and the CSA B64.10 Standard through the CSA Office in Edmonton at (780)
450-2111.
Western Canada Water and Waste Water Association also has an excellent
reference book on backflow prevention. It can be obtained by writing to
Western Canada Water & Wastewater Association at Suite 203, 301 - 14 Street
N.W., Calgary, Alberta. T2N 2A1.
Our Industry
Backflow is generally classified into three groupssevere, moderate
and minor.
Pressure washers with aspirators are generally classified as severe
hazards and require an air gap or a reduced pressure principle backflow
preventer (RP) on the water supply for protection.
A minor hazard would only make the water aesthetically objectionable.
A pressure washer without an aspirator connected to a hose bibb would
qualify for this type of hazard. A simple hose connection vacuum breaker
would suffice to protect the water supply.
Thanks to Roland Tomuschat at Aqualta. He may be reached at (780) 412-6806.
Chemical Dispensers
As dispensing systems connect to the potable water supply, a backflow
preventer is required.
Subject to the conditions that appear below, a Dual Check Atmospheric
Port (DCAP) is the minimum acceptable backflow prevention device that
may be with dispensing units.
-
The proportioner unit is equipped with a manual button which must
be physically held in the open position while the container is being
filled. Note: If the button is lockable, the degree of hazard for
the total installation will increase, therefore a Reduced Pressure
Principal Type Backflow Preventer will be required.
-
The "DCAP" Backflow Preventer will only be subjected to a back-siphonage
condition.
-
The chemical or detergents used will not exceed a moderate hazard
as per the chemical manufacturer's analysis report.
-
The complete installation would be considered a minor hazard based
on the probability of a backflow condition occurring. (A negative
pressure on the water supply line, with simultaneous failure of the
backflow device while the manual button on the proportioner unit is
held in the open position.)
-
If the degree of hazard is in excess of that mentioned in Point
3 or 4 above, a Reduced Pressure Principal Type Preventer shall be
used.
|
|